Abstract:

This research shows the methodology for technical evaluations of the energy performance of absorption refrigeration systems activated with solar energy. This document determines the optimal installation angle of the solar thermal collectors that activate the chiller. Also, the cooling energy Qe, Coefficient of Performance (COP), and hourly Seasonal Coefficient of Performance (SCOP) are determined for each month of the year and recommendations are made for operation in the city of Culiacán, Mexico. The absorption cooling system achieved a Qe of 400.9 kW, a COP of 0.778, and a SCOP of 0.557.