Logotipo ImpactU
Autor

The Active Power Losses in the Road Lighting Installation with Dimmable LED Luminaires

Acceso Abierto

Abstract:

In accordance with the requirements of PN EN 13201-5 standard for road lighting installation, energy performance indicators should be descripted. In order to calculate energy performance indicators, it is necessary to know the active power of the road lighting system. The above standard does not specify whether active power losses should be taken into account in calculations. The main purpose of the article is to estimate the active power losses in the road lighting installation. The article presents methods for calculating active power losses, taking into account losses in all main elements of the installation. The obtained calculation results show the relationship between active power losses and the power of luminaires, their number and spacing between poles. Calculations of active power losses were made for single-phase and three-phase installations. The active power losses in a three-phase system do not exceed 1.5% and in a single-phase installation they may be greater than 7%. Therefore, in order to obtain exact values of energy performance indicators (and also predict electricity consumption), active power losses should be taken into account in calculations. In addition, a comparative analysis of the effect of luminaires dimming and active power losses on annual CO2 emissions was made. Not taking into account the active power losses in the calculation of the lighting installation’s power, for single-phase installations in particular, understates the calculated value of CO2 emissions by more than 6%.

Tópico:

Impact of Light on Environment and Health

Citaciones:

Citations: 6
6

Citaciones por año:

Altmétricas:

Paperbuzz Score: 0
0

Información de la Fuente:

SCImago Journal & Country Rank
FuenteSustainability
Cuartil año de publicaciónNo disponible
Volumen10
Issue12
Páginas4742 - 4742
pISSNNo disponible
ISSN2071-1050

Enlaces e Identificadores:

Artículo de revista